Objective:

To mitigate fire risks in the growing number of mechanical/automated parking systems in residential, commercial, and institutional buildings.

Major Provisions:

Detection and Alarm

  • Smoke and heat detectors must be installed at each parking level, including ramps.
  • These detectors must be part of an addressable fire alarm system.

Fire Suppression

  • Sprinkler systems must cover:
    • Parking floors
    • Vehicle lifts and stackers
    • Pit areas of automated systems
  • Minimum sprinkler density: 10.2 mm/min over 9 m² (per NBC).

Fire Resistance and Structure

  • Mechanical components and shafts must have:
    • 120-minute fire resistance.
    • Fire dampers in HVAC ducts.
  • Fire-rated access doors to vertical shafts.

Emergency Access

  • Dedicated fire exit stairs independent of mechanical shafts.
  • Emergency stairwell to be pressurized and separated by fire-rated walls.
  • Signage and photoluminescent exit paths mandatory.

Ventilation

  • Minimum air change:
    • 6 ACH (Air Changes per Hour) for normal use.
    • Emergency exhaust fans (with fire-rated wiring) to be linked with detectors.

Power Backup

  • 100% DG backup for:
    • Fire pump
    • Fire alarm system
    • Emergency lights
    • Mechanical parking motors (for evacuation of vehicles)

 

You may also like

Leave a Comment

Fire Fighting & Prevention Products

Our Company

The Fire Safety Nation provides Free Fire Safety & Fire Prevention advice portal(In India). Its resource library offers Fire Safety Information as well as fire safety videos. Our goal is to bring important information, news and summarized content of standards like IS, BIS and NFPA to the concerned people.