Special Fire Safety Norms for Vulnerable High-Rise Buildings (Above 90 M)
Objective:
To safeguard occupants of tall buildings where standard evacuation strategies are not sufficient, particularly in the event of high-intensity fires.
Key Safety Requirements:
Firemen Evacuation Lift
- At least one lift per tower must be a firemen’s evacuation lift:
- Capacity: 1000 kg
- Fire-rated doors (2-hour)
- Dual power supply (grid + DG set)
- Firefighter communication phone in the lift.
Dedicated Fire Escape Tower
- Separate fire tower (not common staircase) required:
- Direct access from each floor.
- Fire-rated lobby with positive pressure ventilation.
- No storage or service use allowed.
Refuge Floor Regulations
- Must be provided every 24 meters.
- Clear demarcation, signage, and restricted access.
- Area must be 4–15% of the total floor plate depending on occupancy.
Automatic Fire Systems
- Addressable Fire Alarm System with:
- Voice evacuation announcements
- Flashing strobes for hearing impaired
- Automatic Sprinkler System:
- Zonal control
- Separate pumps and risers per zone
- Water curtain in lift lobbies with glass
Material & Compartmentation
- Fire-rated glass and compartmentation:
- All lobbies, shafts, and electrical rooms.
- Horizontal fire barriers every 40 meters.